Paint Colors
Many colors are available which include Ansi 61 Gray, Ansi
70 Gray and Munsell Green to name a few. Paint colors can even be matched to existing units given the color or
paint chip. All transclosures go through the same rigorous painting process. First the unit shall be
thoroughly scraped and sanded to remove any burrs or welding spatter. The steel shall then be cleaned and
phosphatized under 1800 PSI fluid pressure and treated at 2580F at a distance of 6 inches.
Phosphoric acid shall be Fremont #658 applied at 3/4 of 1% by volume of water. Unit shall be allowed to dry
for 30 minutes.
A red oxide modified alkyd primer shall be applied to unit in an even,
thorough coat. Wet primer thickness shall be 3.0 - 4.0 mils. Dry primer thickness shall be 1.2 - 1.6 mils. A
minimum period of one - two hours should be allowed for prime to dry before recoating.
A modified silicone acrylic alkyd enamel shall be applied a minimum of one -
two hours after the primer has been applied to insure proper bonding. After the first coat is applied allow a
minimum of 2 hours before recoating. After additional coat is applied allow a minimum of 2 hours before
handling the unit. Minimum dry total thickness is 3.0 mils; desired dry total thickness is 3.5 mils.
Paint meets tests specified in ANSI C57.12.28-1988.