Table
1 - Codes for Three-Phase Installed Kvar and System Voltage
|
|
Capacitor
Line-to-line
Voltage
|
Capacitor Bank Three Phase Kvar
Rating |
| 50 |
100 |
150 |
200 |
250 |
300 |
400 |
450 |
600 |
900 |
1200 |
1500 |
1800 |
2400 |
3000 |
|
Code |
|
2400 |
A01 |
B01 |
C01 |
D01 |
E01 |
F01 |
G01 |
H01 |
I01 |
J01 |
K01 |
L01 |
M01 |
N01 |
O01
Note 3 |
|
2770 |
A02 |
B02 |
C02 |
D02 |
E02 |
F02 |
G02 |
H02 |
I02 |
J02 |
K02 |
L02 |
M02 |
N02 |
O02 |
|
4160 |
A03 |
B03 |
C03 |
D03 |
E03 |
F03 |
G03 |
H03 |
I03 |
J03 |
K03 |
L03 |
M03 |
N03 |
O03 |
|
4800 |
A04 |
B04 |
C04 |
D04 |
E04 |
F04 |
G04 |
H04 |
I04 |
J04 |
K04 |
L04 |
M04 |
N04 |
O04 |
|
6600 |
A05 |
B05 |
C05 |
D05 |
E05 |
F05 |
G05 |
H05 |
I05 |
J05 |
K05 |
L05 |
M05 |
N05 |
O05 |
|
7200 |
A06 |
B06 |
C06 |
D06 |
E06 |
F06 |
G06 |
H06 |
I06 |
J06 |
K06 |
L06 |
M06 |
N06 |
O06 |
|
12470 |
A07 |
B07 |
C07 |
D07 |
E07 |
F07 |
G07 |
H07 |
I07 |
J07 |
K07 |
L07 |
M07 |
N07 |
O07 |
|
13200 |
A08 |
B08 |
C08 |
D08 |
E08 |
F08 |
G08 |
H08 |
I08 |
J08 |
K08 |
L08 |
M08 |
N08 |
O08 |
|
13800 |
A09 |
B09 |
C09 |
D09 |
E09 |
F09 |
G09 |
H09 |
I09 |
J09 |
K09 |
L09 |
M09 |
N09 |
O09 |
|
14400 |
Note 2 |
B10 |
C10 |
D10 |
E10 |
F10 |
G10 |
H10 |
I10 |
J10 |
K10 |
L10 |
M10 |
N10 |
O10 |
Note 1:
50 Kvar, 100 Kvar, 200 Kvar, 250 Kvar, and 400 Kvar Three Phase Capacitor Banks will
utilize three phase capacitor units.
All other capacitor banks will utilize single phase capacitor units.
Refer to Table
6 for standard single phase capacitor units used in Type MELP capacitor banks.
Refer to Table
7 for standard three phase capacitor units used in Type MELP capacitor banks.
Note 2: Consult Gilbert Electrical
Systems for
this rating.
Note 3: Fixed bank only. Consult Gilbert Electrical
Systems for
a switched bank alternative. |
|
|
Table
2 - Bank Connections
|
|
Description |
Code |
|
Ungrounded Wye
(for 3 phase, 3 or 4 wire systems) |
U |
|
Grounded Wye
(for 3 phase, 4 wire multi grounded only) |
G |
|
Delta
(for 3 phase, 3 wire systems only) |
D |
|
|
Table 5
- Optional Equipment
|
|
Description |
Code |
|
Group operated three phase disconnect switch with front
operator. (Note 1)
|
S1 |
|
Group operated three phase disconnect switch with side
operator. (Note 1)
|
S2 |
|
Group fusing in addition to capacitor fuses.
|
GF |
|
Current limiting reactors 40 microhenries, 160 amps GES Cat
#43893
|
R |
|
Surge Arresters (Set of three Distribution-class)
|
SA |
|
Key interlock scheme |
K |
|
Pentahead-bolt doors |
P |
|
Control Power Transformer 120Vac secondary
|
T |
|
Unbalance Detection |
U |
| No Optional
Equipment required |
Z |
|
Controller:
|
|
Voltage............................................. |
VC |
|
Current............................................. |
CC |
|
Temperature...................................... |
TC |
|
Time
Clock........................................ |
TT |
|
Power
Factor..................................... |
PFC |
|
Var................................................... |
VAR |
|
Multifunction...................................... |
MFC |
|
Manual............................................. |
MAN |
|
| Paint: |
|
Guardian Green................................. |
GG |
|
Gray ANSI 61.................................... |
GR |
|
Light Gray......................................... |
LG |
|
| Enclosure: |
|
11 gauge mild steel
(standard)............. |
MS |
|
pickled & oiled
steel.......................... |
GS |
|
| Note 1: Switches are provided
for visible break only. |
|
|
Table
3 - Switch Options
|
|
Description |
Code |
|
Switched with three Single phase 200 amp Oil Switches.
Refer to Table
9 for Switch Information.
|
F |
|
Switched with three Single phase 200amp Vacuum
Switches. Refer to Table
9 for Switch Information.
|
V |
|
Switched with three phase Vacuum contactor (Note 1).
Refer to Table
8 for Contactor Information.
|
C |
|
Fixed bank: No switches
|
N |
|
Note 1: Indicates for use on systems up to 5kv
|
|
|
Table
4 - Incoming Cable Configurations
|
|
Description |
Code |
|
Livefront underground
entrance. Includes:
 | provisions for three |
 | single phase terminators |
 | supplied by others |
|
LF |
|
Deadfront radial feed using three 200 amp bushing wells. (Note 1)
|
DF |
|
Deadfront, loop-feed Six 200 amp bushing Wells. (Note
1)
|
DL |
| Note 1: These
devices are to be used for visible disconnection only; they are not designed for
capacitor-load switching. |
|
MELP- Basic letters for series MELP metal enclosed capacitor
assembly
N06- Installed three-phase Kvar and voltage rating
code; select from table 1.
U – Bank connection code; select from table
2
V - Switch option
code; select from table 3
LF - Incoming cable configuration; select from table 4
K-T-MAN-GG-GS - Optional equipment codes: select from table 5
The complete catalog number would be:
MELP-N06UVLF-K-T-MAN-GG-GS