Metal Enclosed Capacitor Options for Industrial Market
Unbalance detection schemes:
There are several unbalance detection schemes and methods. ANSI/IEEE C37.99 shows unbalance detection schemes. This
includes schemes for larger banks and higher voltage banks as well as the methods we have standardized on for
distribution voltages. We have essentially settled on a handful of methods. These are as follows:
I. Floating Wye Connections.
A PT is connected between the neutral of the capacitor wye and the system ground. This method cannot be used on
three phase, three wire systems or three phase, four wire systems with unigrounded neutral. The system has to be
three phase, four wire, and multigrounded. This needs to be ascertained before quoting or, explained in the quote.
Also, this unbalance detection should not be used on resistance grounded systems.
An unbalance detection scheme should be offered on any capacitor bank connected floating wye. At least as an
option. A table should be provided to show the unbalance percentage of units as capacitors fail in a phase to
emphasize the problem.
This method will be affected by system unbalances and the relay will require harmonic restraints on filter
banks.
See details on article GES6233
II. Grounded Wye Connections
A CT is connected between the neutral point of the capacitor bank to the system ground. The grounded wye
connected capacitor bank can only be used on the three phase, four wire multigrounded system and this unbalance
detection scheme is limited to grounded banks.
Unbalance detection schemes for grounded wye bank are not to be considered as normal options. Also, this
detection scheme should not be used on filter applications.
This detection scheme will be affected by system unbalances.
See details on article GES7233
III. Split Wye Connections
Normally a CT is used, connected between the neutrals of two wye capacitor sections. The wye sections are
generally equal, but do not have to be so. There are some customers that prefer a PT to read the unbalance.
Either way the neutral bus will not be affected by system problems such as system unbalances and harmonics. The
relay does not have to have harmonic restraints for this connection.
This method can be used on any three-phase system.
See details on article GES19233
IV. Delta Connections
CT’s are mounted in the line connected to the capacitors. We can use two or three CT’s for the sensing. See
GES delta unbalance paper. The CT’s will sense a drop in current when a capacitor fails in a leg.
This method can be used on any three-phase system.
This detection scheme will be affected by system unbalances.
See details in article GES4233
|