There are several different approaches and customer options for incoming sections. Some of these are as follows:
Control power transformer (CPT), if required, will be placed in the section.
Top entry can also be supplied in place of bottom entrance. Top entry into
the enclosure can be supplied with roof bushings or with conduit connections. With a disconnect switch, additional
bus-work will be required.

NEC section 420-24 (b)
(1)&(2) requires isolating means. This can be in the capacitor bank, in upstream switchgear, or drawout circuit
breakers. They should also be interlocked so the isolation switch does not break the capacitor load.
If fuse cutouts (or similar) are used and they cannot be interlocked, refer to NEC section 490-22. A prominent sign
is to be displayed stating not to open this device under load.


The
best placement for main fuses, arresters, or other main bank protection would be at the "Point of Common Connection
(PCC)." This will allow protection for the whole line from the PCC to the capacitor bank.